HindlePower Atevo Series Operating/Service Instructions Manual page 205

Microprocessor-controlled float battery charger three phase input 16-1000 adc output
Hide thumbs Also See for Atevo Series:
Table of Contents

Advertisement

HindlePower Inc
Wiring
Wiring
• Connect wire from twisted-pair designated as 'DC(+)
REMOTE SENSE (TB1).
• Connect wire designated as 'DC( – )
• Observing correct polarity, connect battery end of 'DC(
location on the battery.
• Confirm polarity, and connect battery end of 'DC( – )
on the battery.
• Verify polarity of POS and NEG battery connections.
• DO NOT energize ATevo until you configure Remote Sense jumpers per
• After Remote Sense Jumpers have been correctly configured, replace the safety shield and
re-energize ATevo.
Notes
Notes
• Maximum current is 150mA.
• Run the twisted-pair cable with the sense leads in a dedicated conduit.
• Fuse each of the sense wires.
Copyright HindlePower Inc. 2021
DC(+)' to 1- 1-POS
DC( – )' to 3- 3-NEG
NEG (negative) terminal of TB1.
DC( – )' wire to a negative(-) sense location
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en
POS (positive) terminal of
DC() ) ' wire to a positive () sense