HindlePower Atevo Series Operating/Service Instructions Manual page 241

Microprocessor-controlled float battery charger three phase input 16-1000 adc output
Hide thumbs Also See for Atevo Series:
Table of Contents

Advertisement

HindlePower Inc
12.6.5.
12.6.5. Analog Input Alarm and Trigger
Analog Input Alarm and Trigger
Assignment
Assignment
The ATevo can generate alarms based on analog input values. There are several triggers that
can be assigned to define the alarm condition. An alarm can be generated if the analog value is
above a threshold, below a threshold, within a defined range, or outside a defined range. The
threshold parameter(s) required will depend on the trigger type selected. Threshold parameters
must be entered based on the scaling values such that the thresholds assigned are within the
range of the scaling.
To assign an alarm trigger to an analog input:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input (refer to
'Trigger:' > select desired option
Copyright HindlePower Inc. 2021
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en
Section
Last modified: 2 August 2023
12.6.1) >
Page 241 of 311