HindlePower Atevo Series Operating/Service Instructions Manual page 203

Microprocessor-controlled float battery charger three phase input 16-1000 adc output
Hide thumbs Also See for Atevo Series:
Table of Contents

Advertisement

HindlePower Inc
11.3.
11.3. Procedure for Wiring Remote
Procedure for Wiring Remote
Sense
Sense
Route twisted-pair cable between the battery and ATevo. Make the connections listed below
befor
before e moving the Remote Sense enable jumpers to enable the Remote Sense.
Preparation:
Preparation:
• Open both front panel breakers (CB1/CB2).
• De-energize and lock out all ac and dc voltages to ATevo.
• Allow internal voltages to dissipate.
• Use #16 AWG twisted-pair wire, of appropriate length to reach from the battery to ATevo.
• Designate, or label
label, one (1) wire of twisted pair as 'DC(+)
• Designate the other wire of the twisted pair as 'DC( – )
• Route one (1) end of the twisted pair remote sense wiring to BATTERY, at the desired
battery sense location.
• Open ATevo front panel door, and remove safety shield.
• Verify no hazardous voltages are present with a voltmeter.
• Locate Remote Sense terminal block inside ATevo:
• Route other end of twisted pair remote sense wiring to ATevo 3-position REMOTE SENSE
terminal block.
Style-5070
Style-5070
• Remote Sense terminals are on located on the center-front I/O panel pcb (A9), next to the