Battery Open Test Settings; Running Battery Open Tests Periodically; Running Battery Open Test Manually - HindlePower Atevo Series Operating/Service Instructions Manual

Microprocessor-controlled float battery charger three phase input 16-1000 adc output
Hide thumbs Also See for Atevo Series:
Table of Contents

Advertisement

HindlePower Inc
7.7.
7.7. Battery Open Test
Battery Open Test
The Battery Open Test feature will detect if the connection between the battery and ATevo has
been lost, or if there is a weak or faulty battery. The test lowers the charger voltage and
verifies whether the battery can assume the present dc load. This test can be run manually or
according to a set schedule.
The Battery Open Test will fail if the dc bus drops below a configurable voltage set point. When
such occurs the test aborts immediately and ATevo will raise output voltage back to the present
Float or Equalize setting. Test duration is configurable as seen below.
If the test fails, a Battery Open alarm is generated and can only be cleared by the Unlatch
Battery Open Alarm control.

Battery Open Test Settings

Running Battery Open Tests Periodically

Running Battery Open Test Manually

Resetting Battery Open Alarm
Copyright HindlePower Inc. 2021
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en
Last modified: 3 August 2023
Page 171 of 311

Advertisement

Table of Contents
loading

This manual is also suitable for:

Atevo o&si-3ph

Table of Contents