2.7. Wiring ATevo Common Alarm
Wiring ATevo Common Alarm
ATevo Main Control Board (A1) is equipped with a 'summary' Common Alarm relay. This relay
contact transfers when any one (1) or more of the standard ATevo alarm(s) become active. One
(1) set of form-C alarm contacts is provided, and are accessible via terminal block (A1-TB6) on
the Main Control Board. Refer to figure below.
PROCEDURE
PROCEDURE
1. Allow 30in / 762mm of wire inside enclosure, and trim excess.
2. Route annunciator wires to ATevo front panel door by following existing harness past door
hinge.
3. Use two (2) wire ties and allow a 4-6in / 102-153mm loop for the hinge.
4. Trim wires to length to connect to alarm terminal block (A1-TB6), and strip 0.25in / 6.4mm
of insulation.
5. Make connections at A1-TB6 and tighten compression screws.