12.6.6.
12.6.6. Analog Input Alarm Threshold
Analog Input Alarm Threshold
Assignment
Assignment
ATevo can generate alarms based on analog input value. Alarm thresholds are the set points at
which an alarm occurs. Each analog input can be assigned an alarm with a trigger. Some
triggers only require one threshold. The 'above a threshold' alarm trigger requires a 'high
threshold' set point, the 'below a threshold' trigger requires a 'low threshold set point'. Other
range based triggers require both a 'low threshold' and a 'high threshold' set point to
determine the range. ATevo will automatically determine which thresholds are required based
on the trigger selected. Always set the trigger before adjusting the thresholds.
To adjust the low level threshold set point for a trigger for an analog input alarm:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input (refer to
'Trigger:' > 'Low threshold:' > set digits
*
This number may be in primary values based on the scaling settings for the
associated analog input. The threshold set point configured will be scaled by the
associated analog input scaling.
To adjust the high level threshold set point for a trigger for an analog input alarm:
MENU > AUX INPUTS > 'Analog Input Configuration' > select input (refer to
'Trigger:' >'High threshold:' > set digits
*
This number may be in primary values based on the scaling settings for the
associated analog input. The threshold set point configured will be scaled by the
associated analog input scaling.