HindlePower Atevo Series Operating/Service Instructions Manual page 45

Microprocessor-controlled float battery charger three phase input 16-1000 adc output
Hide thumbs Also See for Atevo Series:
Table of Contents

Advertisement

HindlePower Inc
2.5.
2.5. Making DC Output Connections
Making DC Output Connections
Installer is responsible to provide suitable dc output, battery, and dc load wiring.
Guidelines for DC Connections
Guidelines for DC Connections
Follow these steps to connect the battery to ATevo:
1. Size the dc wiring to minimize voltage drop. Acceptable wire size depends on the
installation. As a guideline, voltage drop should not exceed 1% of nominal output voltage
at full current. Refer to the following table to determine the voltage drops for various wire
sizes, currents and distances.
Voltage Drop per 100ft / 30.5m of Wire (for copper at 68 F / 20 C)
W W ir ire Size (
e Size (A A WG
10
10
8 8
6 6
4 4
2 2
0 0
Example: 100ft / 30.5m of #8 AWG wire at 50A has a 3.1V drop.
Example
2. ATevo is factory wired to regulate output voltage at the output terminals. If total voltage
drop is greater than 1% (e.g. 1.3V for a 130 Vdc system), remote sense wiring is
recommended (refer to
3. Do not run external ac and dc power wiring through the same conduit.
4. Facility-specific installation requirements take precedence.
PROCEDURE
PROCEDURE
1. Identify your ATevo enclosure type (Style-5070, Style-5030, Style-163, or Style-198). Refer
to the applicable image in the sections below.
2. Use a dc disconnect switch or circuit breaker between ATevo and the dc bus. This device
should have lockout capability to allow ATevo to be disconnected from the dc bus for
maintenance.
Copyright HindlePower Inc. 2021
W W ir ire Sizing Chart
e Sizing Chart
WG) )
30
30
40
40
50
50
3.0V 4.0V 5.0V not recommended not recommended
1.9V 2.5V 3.1V not recommended not recommended
1.2V 1.6V 2.0V 3.0V
0.7V 1.0V 1.2V 1.9V
0.5V 0.6V 0.8V 1.2V
0.3V 0.4V 0.5V 0.7V
Section 11
).
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en
DC Curr r ent (Amper
DC Cur
ent (Amperes)
es)
75
75
100
100
not recommended
2.5V
1.6V
1.0V
Page 45 of 311