1. Alarm contacts are rated at 0.5A / 125 Vac or Vdc.
2. Common Alarm relay terminal block (A1-TB6) is compression type, accepting wire sizes
#22-14 AWG.
3. Terminals are labeled in the non-alar
relays energized.
*
Not 'shelf state'
4. If user alarm contacts (A1-TB6) are to drive inductive dc loads (e.g. a larger dc relay) an
external protective diode must be installed at the dc relay to avoid equipment damage.
Refer to Application Note
Application Note (JD5011-00).
Copyright HindlePower Inc. 2021
non-alarm m condition, with ATevo operating 'normally' and
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en