13.5.3.
13.5.3. Forced Load Sharing Alarms
Forced Load Sharing Alarms
The following alarms related to Forced Load Sharing are logged and can be configured to
trigger the common alarm:
• 'Loadshare Not Ready' – displays on ATevo that is not ready to share load for reasons
including no ac power, low ac power, HVDC shutdown, HLD shutdown, or open DC Breaker
(CB2)
• 'Loadshare Comm Failure' – displays when an ATevo configured for Forced Load Sharing is
not receiving any load share messages
• 'Loadshare Indep Mode' – indicates virtual independence between Forced Load Sharing
ATevos, only reported on the Primary ATevo