HindlePower Inc
5.1.3.
5.1.3. Changing Equalize Method
Changing Equalize Method
The EQUALIZE METHOD button switches the equalize method between MANUAL TIMER and
AUTOMATIC TIMER. The present equalize method is displayed at the top right of the HOME
screen
• ' Eqlz Mthd: Man ' specifies MANUAL TIMER
• ' Eqlz Mthd: Auto ' specifies AUTOMATIC TIMER.
To change the Equalize Method:
EQUALIZE METHOD > select other displayed option
When AUTOMATIC TIMER is selected, ATevo will:
• Automatically switch to EQUALIZE mode when power is restored after a loss of AC power
for greater than 12 seconds.
• Start EQUALIZE TIMER.
• Remain in EQUALIZE mode until either the EQUALIZE TIMER expires or the charge mode is
switched back to float mode manually.
When MANUAL TIMER is selected, ATevo will only switch to EQUALIZE MODE when the
mode is manually changed.
*
EQUALIZE METHOD button is in same relative location as EQLZ MTHD button on
legacy AT30 chargers. Functionality is equivalent in that when pressed, it
changes the equalize method. The Manual Equalize Method (no timer) available
in legacy AT30 chargers is not supported by ATevo.