11.5.
11.5. Disabling Remote Sense
Disabling Remote Sense
If you need to temporarily disable Remote Sense:
• De-energize and lock out all ac and dc voltages within the ATevo enclosure.
• Check with a voltmeter.
• Remove the safety shield.
• Move SHORTING BLOCKs to Local Sense configuration per
• Replace safety shield and close front panel door.
• Re-energize ATevo.
*
If Remote Sense is to be disabled for extended periods of time or permanently
disabled, it is highly recommended that the sense leads (the twisted pair cable)
be disconnected from both the battery and terminal block (A2-TB1).