4.10.2.
4.10.2. Setting Up Ground Imbalance
Setting Up Ground Imbalance
Alarm
Alarm
To change the imbalance alarm (measured in Vdc), press MENU, then select GROUND ALARM:
• Navigate to Vgnd Imbalance W
Vgnd Imbalance War arning
• Select it with EDIT/ENTER.
• Press UP and DOWN to change setting value.
• Once desired setting is displayed, press EDIT/ENTER to store it.
• Repeat process for Vgnd Imbalance Critical
*
For further information regarding ATevo ground alarms, including instructions for
locating and identifying faults, refer to supplemental instructions (JA5124-09
and/or JD5032-00).
Copyright HindlePower Inc. 2021
ning using UP and DOWN.
Vgnd Imbalance Critical.
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en