HindlePower Atevo Series Operating/Service Instructions Manual page 213

Microprocessor-controlled float battery charger three phase input 16-1000 adc output
Hide thumbs Also See for Atevo Series:
Table of Contents

Advertisement

HindlePower Inc
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en
12.1.3.
12.1.3. Analog Inputs
Analog Inputs
The four (4) Analog Inputs are rated for 0-10 Vdc. They utilize a common ground, referenced to
DC OUTPUT NEG, and can be used to import generic analog values. ATevo assigns each Analog
Input a unique generic name such as 'AUX 1 input AN1'. This name can be changed to be
readily identifable by the end user (e.g. 'Ambient Temp'). ATevo will report all status and alarms
with the default name or the custom name assigned.
The Analog Inputs include scaling configuration such that ATevo can report their values in
primary units. For example, a temperature transducer with a 0 to 10 Vdc output can be
configured to scale the voltage value directly to the associated temperature represented by the
dc voltage. The associated 'units' name can also be configured such that when the Analog
Input value is displayed, it will display as '80.3 F' instead of '6.2 Vdc'.
Each Analog Input can be configured to generate alarms based on its value. Available trigger
conditions to generate an alarm include below a threshold, above a threshold, within a range,
or outside a range. Threshold and range values are configurable, and are entered in the
primary units (such as °F) based on scaling configuration.
Last modified: 1 August 2023
Copyright HindlePower Inc. 2021
Page 213 of 311

Advertisement

Table of Contents
loading

This manual is also suitable for:

Atevo o&si-3ph

Table of Contents