7.6.
7.6. Resetting Latched Alarm Relays
Resetting Latched Alarm Relays
Latched alarm relays can be reset or cleared two (2) different ways.
• The Legacy AT30 method may be used by pressing and holding the UP arrow button for a
few seconds. This will reset or clear all latched alarm relays. A brief confirmation message
will display.
• Individual latched alarm relays or all latched alarm relays may also be reset via the
RELAYS icon from the Main Menu.
To reset an individual latched alarm relay: MENU > RELAYS > 'Unlatch selected relays' > select
latched relay from list
To reset all latched alarm relays: MENU > RELAYS > 'Unlatch all relays (x)', where 'x'
represents the number of presently latched relays.
Copyright HindlePower Inc. 2021
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en
Page 169 of 311