11. Connect the TempCo cable to ATevo.
• Locate TB8 and insert one (1) of the stripped wires from the twisted pair into each
position of terminal block (A2-TB8). Connection Points are not polarity sensitive.
• Locate the EARTH quick-connect terminal. Carefully pull off the quick-connect terminal
and wire from the EARTH terminal.
• Plug the quick-connect terminal attached to the end of the TempCo cable's shield wire
onto the Power Board's EARTH terminal.
• Connect the quick-connect terminal removed from the EARTH terminal to the Piggy Back
terminal on the end of the TempCo cable's shield wire.
• Fasten the TempCo cable to existing wire harness with plastic wire ties.
12. At the battery, connect the quick-connect terminals to the TempCo probe (A10).
Connection points are not polarity sensitive.
13. Coil up and wire-tie any excess wire to prevent damage.
14. Confirm that:
• All connections are secure.
Copyright HindlePower Inc. 2021