HindlePower Atevo Series Operating/Service Instructions Manual page 193

Microprocessor-controlled float battery charger three phase input 16-1000 adc output
Hide thumbs Also See for Atevo Series:
Table of Contents

Advertisement

HindlePower Inc
10.2.
10.2. Installing the TempCo Option
Installing the TempCo Option
In overview, there are four (4) stages. The full detailed procedure is found below:
• Mount probe assembly (A10) on or near battery.
• Install interconnection cable from probe assembly to ATevo.
• Wire charger-end of cable to ATevo Power Board (A2-TB8).
• Configure ATevo to recognize the TempCo option.
The TempCo probe (A10), or 'puck', is the same for all battery types and all ATevo models,
regardless of dc output voltage. TempCo accessory kits (p/n EJ5304-##) differ, depending on
cable length (25ft, 50ft, 100ft, etc.).
PROCEDURE
PROCEDURE
1. Turn off (open) both ATevo front panel breakers (CB1/CB2).
2. De-energize and lock out all ac and dc voltages to ATevo.
3. Allow internal voltage potentials to dissipate.
4. Remove safety shield and verify no hazardous voltages are present with a voltmeter.
5. At the battery location, mount the probe (A10) on a clean, dry surface on or as close to
battery as possible.
!
Do NOT
NOT mount probe on: unpainted wood, bare galvanized metal, or plastic
surfaces. Consult battery manufacturer for mounting restrictions and adhesive
compatibilities.
6. To apply probe, clean mounting surface with isopropyl alcohol and dry thoroughly.
7. Remove protective backing from double-faced adhesive tape on probe.
8. Press adhesive onto surface.
9. Install supplied cable:
• Route end of cable that has two (2) stripped wires and a quick-connect terminal to the
inside of ATevo enclosure.
• Leave 30in / 762mm of cable inside enclosure.
• Run cable through a conduit that does not contain power wiring.
• Route other end of cable to probe at the battery.
• Coil up excess cable.
• Make sure all wiring conforms to NEC, local, and site requirements
10. Route the interconnection cable to ATevo signal terminal block (TB8) marked 'BA
as shown in the images below:
Copyright HindlePower Inc. 2021