5.4. High Level Detect

High Level Detect
ATevo High Level Detect has a dedicated hardware circuit that detects if the dc bus voltage is
above a configurable set point. If the dc voltage rises above the set point threshold for more
than 30 seconds, the circuit disables the output drivers (rectifier controllers) and forces the
Common Alarm Relay to the active state.
The High Level Detect is a true failsafe feature in that it can shut down the charger by disabling
the rectifier control signals. This
circuit works independent of the microprocessor and will override the rectifier control. The High
Level Detect will shut down the charger output circuitry should a catastrophic microprocessor
failure occur, turning the rectifier to the full on condition.
If the High Level Detect shutdown occurs, the circuit latches until the charger is restarted by
recycling both the AC Input (CB1) and DC Output (CB2) Circuit Breakers. The High Level Detect
circuit has a dedicated Analog High Level Detect Shutdown alarm LED, that illuminates if the
High Level Detect condition is triggered. The Analog High Voltage Shutdown alarm LED is on
the Main Control Board. You will need to open ATevo's front panel door to view the Analog High
Voltage Shutdown alarm LED.
Refer to the following sections to learn about:
Section 4.9, Enabling/Disabling High Level Detect
Section 4.3.3, Setting High Level Detect Threshold
Copyright HindlePower Inc. 2021
ATevo O&SI - 3PH Input (16-1000 Adc) - 1.1_en
Last modified: 3 August 2023
Page 130 of 311