HindlePower Atevo Series Operating/Service Instructions Manual page 260

Microprocessor-controlled float battery charger three phase input 16-1000 adc output
Hide thumbs Also See for Atevo Series:
Table of Contents

Advertisement

HindlePower Inc
13.8.
13.8. Timed Equalize with Forced Load
Timed Equalize with Forced Load
Sharing
Sharing
If a timed equalize is in progress, all ATevos sharing load will depict the Equalize Time
Remaining, alternating with the Volt/Ammeter display. If the ATevos go independent while timed
equalize is active, they will continue timed equalize. If a Primary ATevo goes offline, the
Secondary ATevo will continue in equalize mode until the Primary ATevo come back on-line. The
Primary ATevo and all Secondary ATevos will switch back to float mode after the Primary ATevo
resets.