Cable Specification List - ABB HVC-R 100/150 V2 Installation Manual

E-bus charger
Table of Contents

Advertisement

4.4.7. Cable specification list

Tables below provide general specifications of the required cables. Use these tables to select
cables, taking into account local installation environment, cable length, cable temperature
rating, losses and local regulations.
AC and DC power cables
Functional description
DC Power cable
Number of cores
1
Cross section
95 – 185 mm
Min – Max external
22 – 32 mm
diameter to fit through
gland
Shielding
No
Conductor
Tinned copper or
aluminum conductor, fine
wire
stranded acc. to VDE
0295 cl.5/IEC Cl.5
Insulation
Special rubber or PVC
(outdoor use, UV-
protected, oil resistant)
Minimum Nominal
600/1000 Vac
Voltage Uo/U
900/1500 Vdc
Minimum Test Voltage
6 kV
[AC]
Ambient Temperature
-40ºC to 80ºC, permissible
range
conductor operating
temperature +90°C
Core identification
Data cables
Functional
Interlock cable
description
Number of cores
4
Twisted pairs
Yes (2 x 2)
Cross section
0.75 – 2.5 mm
Min – Max external
8 – 9 mm
diameter to fit
through gland
Shielding
Yes (tinned
copper braid)
Conductor
Fine strand
copper wire
Insulation
PVC or other
material that
can be used
outdoor and
are UV-
protected
120 Ω ± 10%
Characteristic
impedance
Minimum Test
1.5 kV
Voltage [AC]
Ambient
-40ºC to 70ºC
Temperature range
Core identification
Acc. to DIN
47100
Document: v0.1 / Document No.: TBA | Date: XX-08-2021
PE cable
1
2
2
35 mm
6 – 12 mm
No
Fine strand copper wire
acc. to VDE 0295 Cl. 5/
IEC 60228 Cl. 5
Special PVC (outdoor
use, UV-protected, oil
resistant)
450/750 Vac
4 kV
-40ºC to 70ºC
gn/ye
Ethernet (S/FTP,
Ext. Beacon
CAT6)
cable
8
4
Yes (4 x 2)
No
2
2
0.25 – 0.75 mm
0.5 – 0.75 mm
5 – 10 mm
5 – 6 mm
Yes (tinned copper
No
braid)
Fine strand copper
Fine strand
wire
copper wire
PVC or other
PVC or other
material that can
material that can
be used for
be used for
industrial and
industrial and
outdoor
outdoor
applications, and
applications,
are UV-protected
and are UV-
protected
100 Ω
700 V
2 kV – 4 kV
-40ºC to 70ºC
-40ºC to 70ºC
TIA/EIA-568-B.1-
Numbering or
2001 T568A
color
HVC-R 100/150 V2 E-Bus Charger Installation Guide
AC auxiliary power cable
3
2
2.5 mm
6 – 12 mm
No
Bare copper, fine wired,
bunch stranded acc. to
VDE 0295 Cl.5/IEC Cl.5
Special PVC (outdoor use,
UV-protected, oil resistant)
450/750 Vac
4 kV
-40ºC to 80ºC
Acc. to IEC 60446
Ext. Stop
button cable
2
No
2
0.5 – 0.75
2
mm
5 – 6 mm
No
Fine strand
copper wire
PVC or
other
material that
can be used
for industrial
and outdoor
applications,
and are UV-
protected
2 kV – 4 kV
-40ºC to
70ºC
Numbering
or color
Page 52 of 133
Ext. EMO
cable
4
No
0.5 – 0.75
2
mm
5 – 6 mm
No
Fine strand
copper wire
PVC or
other
material that
can be used
for industrial
and outdoor
applications,
and are UV-
protected
2 kV – 4 kV
-40ºC to
70ºC
Numbering
or color

Advertisement

Table of Contents
loading

Table of Contents