3.6. Geometry of infrastructure

3.6.1. Space required for the Power Cabinet

A single HVC 100/150 V2 Power Cabinet requires a minimum space of 1170 x 2070 mm (W
x D) or 1370 x 1970 mm (W x D). This space is calculated as follows:
A cabinet footprint of 1170 x 770 mm.
The unoccupied space around the cabinet regarding the following:
100 mm at the rear side or 0 mm at the rear side when both left and right side
have a minimum free space of 100 mm.
100 mm or 0 mm at the left side, if another Power Cabinet is placed next to it.
100 mm or 0 mm at the right side, if another Power Cabinet is placed next to it.
1200 mm at the front side in order to open the front door. If the cabinet is placed
indoors, consider designating additional free space in front of the open door
(escape way for service people).
The cabinet needs at least the opening area of the front and rear side
with a minimum free distance of 100 mm. This means that cabinets can
stand in a row with one or both side entries blocked (distance on
left/right side is 0 mm).
It is also possible for the cabinets to stand back-to-back (distance on
the rear side is 0 mm). In this case both side entries must have a
minimum free distance of 100 mm. If this is not the case, then the air
supply is not sufficient.
Overview of Power Cabinet's ventilation system
The HVC 100/150 V2 is equipped with 4 air inlets (A) on all sides of the cabinet and an air
outlet (B) at the front to allow airflow inside the cabinet. Do not place any objects that may
obstruct the airflow near the air inlets or outlet (see also Caution above). If necessary, take
precautions to prevent snow, sand or dust from blocking the inlets or outlet.
Document: v0.1 / Document No.: TBA | Date: XX-08-2021
HVC-R 100/150 V2 E-Bus Charger Installation Guide
CAUTION
Page 28 of 133