Cable Specification List - ABB HVC-PD Installation Manual

Hide thumbs Also See for HVC-PD:
Table of Contents

Advertisement

4.4.5. Cable specification list

Tables below provides general specifications for the needed cables. Use these tables to select
cables, taking into account local installation conditions, cable length, cable temperature rating,
losses and local regulations.
AC and DC power cables
Functional description
Number of cores
Cross section
Min – Max external
diameter to fit through
gland
Shielding
Conductor
Insulation
Nominal Voltage Uo/U
Test Voltage
Ambient Temperature
range
Core identification
Data cables
Functional description
Number of (twisted) pairs
Cross section
Min – Max external diameter to fit
through gland
Shielding
Conductor
Insulation
Test Voltage
Ambient Temperature range
Core identification
Important: all cables must be resistant to being placed in the ground, submerged in
conduit.
All cables must have and isolation that are self-extinguishing and flame retardant
according to UL VW-1, CSA FT1.
All cables must meet the UL and the RoHS compliance.
The identity and/or function must be marked on every 78.74 Inch of the cables and
on both ends.
Document: V1.2 / Document No.: 6AGA000008-0629-EN | Date: 06-30-2022
DC Power cable
1
350 – 600 MCM
0.75 – 1.10 Inch
No
Tinned copper or
aluminum conductor, fine
wire
stranded acc. to VDE
0295 cl.5/IEC Cl.5
Special rubber or PVC
(outdoor use, UV-
protected, oil resistant)
600/1000 Vac
900/1500 Vdc
6 kV
-40ºC to 80ºC,
permissible conductor
operating
temperature +90°C
Interlock cable
2 x 2
18 – 14 AWG
0.20 – 0.39 Inch
Yes (tinned copper braid)
Fine strand copper wire
PVC or other material that can be
used outdoor and are UV-
protected
1.5 kV
-40ºC to 70ºC
Acc. to DIN 47100
HVC‐PD E‐Bus Charger Installation Guide 
GND cable
AC utility power cable
1
4
2 AWG
14 AWG
0.51 – 0.83 Inch
0.20 – 0.39 Inch
No
No
Fine strand copper wire
Bare copper, fine wired,
acc. to VDE 0295 Cl. 5/
bunch stranded acc. to
IEC 60228 Cl. 5
VDE 0295 Cl.5/IEC Cl.5
Special PVC (outdoor
Special PVC (outdoor
use, UV-protected, oil
use, UV-protected, oil
resistant)
resistant)
450/750 Vac
450/750 Vac
4 kV
4 kV
-40ºC to 70ºC
-40ºC to 80ºC
gn/ye
Color Acc. to IEC 60446
CAN cable
1 x 2
20 – 18 AWG
inapplicable
Yes (tinned copper braid)
Fine strand copper wire
PVC or other material that can be
used outdoor and are UV-
protected
1.5 kV
-40ºC to 70ºC
Acc. to DIN 47100
Page 52 of 146