Connecting The Communication Ethernet Cable (Input) - ABB HVC-R 100/150 V2 Installation Manual

E-bus charger
Table of Contents

Advertisement

4. Shorten the InterLock cable to the correct length – allowing to reach the terminal block
X4. Do not make the cable routing too tight, or too loose.
5. Tighten the nut of the gland to secure the InterLock cable.
6. Strip 11 mm of the insulation from the ends of the wires.
7. Tighten the shield of the Interlock cable into a thread and slide a shrink tubing over the
it.
8. Crimp ferrules to the ends of the wires.
9. Loosen the connector screws.
10. Insert the wires of the InterLock cable into the connectors of the terminal block X4.
Refer to the table below:
Functional description
Interlock In
Interlock Out
DC Guard A
DC Guard A GND
Interlock GND
See also Appendix F Signal connection diagram.
5.14.11.

Connecting the communication Ethernet cable (input)

Information in this chapter refers to the communication cables connecting the Dual Depot
Charge Box to the Power Cabinet or a preceding Dual Depot Charge Box.
1. Loosen and remove the cable gland's (#15) nut for the communication Ethernet cable.
2. Insert the communication cable into the cable gland (#15) and tighten the cable gland's
nut to secure the cable(s).
Location of terminal X11 and instructions on the connection.
3. Route the Ethernet cable to the terminal X11 (refer to the picture above for the
preferred cable route). Do not make the cable routing too tight, or too loose.
4. Plug the cable's RJ45 connector into the terminal X11's socket.
5. Tighten the nut of the gland to secure the Ethernet cable.
Document: v0.1 / Document No.: TBA | Date: XX-08-2021
HVC-R 100/150 V2 E-Bus Charger Installation Guide
Connector
Wire color
X4-4
White
X4-5
Brown
X4-8
Green
X4-9
Yellow
X4-1
Shield
Page 104 of 133