Interlock Cable Recommendations; Signal Connections; Alarm Outputs - ABB Integritas Quick Start Manual

Table of Contents

Advertisement

QUICK START GUIDE
Information: Battery Monitoring Connections - for use with NiCd and Lead acid
batteries (VRLA, Flooded)
Battery Monitoring is accomplished with a "Daisy Chained" series of probes. The Probes monitor battery
temperature. Bolt the Probe under the "–" terminal connector hardware; NOT under the connecting lug.
Max per system: Probes - 16.
Ordering Codes
1600093513A
1600093512A
Information Interlock Cable Recommendations
• Wire - 20-24 AWG
• Mating Connector: Molex housing - 43025- 0200,
• Terminals - Molex 43030-0008 (15µ"gold plated)
• Hand Crimp Tool - Molex 0638190000
• Insertion Tool - Molex 0638120800
• Extraction Tool - Molex 0011030043
Information: Signal Connections.
Alarm Relays Factory set to Open On Alarm. Rated 125V (60V for 24V and 48V chargers), 0.5A.
"Dry" No Voltage Binary Inputs Require a contact closure to Common (pin 2).
"Dry" 24V Biased Binary inputs Require a contact closure to 24V Source (pin 2).
Connector
Description—Signal on Pin 1
TB1
Power Critical Alarm
TB2
Power Major Alarm
TB3
Power Minor Alarm
TB4
Alarm R1 (default is RFA/MRFA)
TB5
Alarm R2 (default is ACFMACF)
TB6
Alarm R3 (default is BD/VLV)
TB7
Alarm R4 (default is GFI)
TB8
Alarm R5 (default is SPD, DC, and AC)
TB9
Alarm R6 (default is BTA "Battery Test Active")
TB10
Alarm R7 (default is "Check Battery")
Page 22
© 2021 ABB. All rights reserved.
Battery Temperature Measurement
Pulsar XL Alarm Outputs
Descriptions
DTP873-Battery Thermal Probe
DTP873-Ambient Probe
Pin 2
Common
Common
Common
Common
Common
Common
Common
Common
Common
Common
Version 6.0