Cable Specifications; Torque Specification - ABB Terra 94 UL Operation And Installation Manual

Table of Contents

Advertisement

"Operation and installation manual" - "Terra 94/124/184(NEVI) UL"
76

10.2 Cable specifications

AC Input
AC cable cross section
AC connection type
AC cable diameter (cable entry plate)
Insulation
Protective Earth (PE)
PE cable cross section
PE connection type
PE cable diameter (cable entry plate)
Insulation
Ethernet
CAT
Ethernet cable diameter (cable entry plate)
Insulation
Tilt sensor (option)
Number of wires
Max. Wires cross section
Cable diameter (cable entry plate)
Insulation

10.3 Torque specification

Parameter
Fasteners for the PE wire
Fasteners for the L1, L2, L3
Tilt sensor screw terminal block
Fasteners for the connection of the EVSE to the base
(M12 bolt)
350 MCM (copper) each phase (recommended)
M10 (
) cable lug
25 / 64
...1
in (21...40 mm)
53 / 64
37 / 64
PVC or other material that is serviceable for
outdoor, UV-protected and suitable for use in
underground ducts
Select the Ground (PE) wire size per NEC or local
electric code
M12 (
) cable lug
15 / 32
...1
in (21...40 mm)
53 / 64
37 / 64
PVC or other material that is serviceable for
outdoor, UV-protected and suitable for use in
underground ducts
CAT 5e (recommend)
CAT 6 (high presence of electromagnetic
interference and/or noise)
...
in (10...17 mm)
25 / 64
43 / 64
PVC or other material that is serviceable for
outdoor, UV-protected and suitable for use in
underground ducts
4 (2 wires for power supply and 2 wires for relay
contacts)
12 AWG (4 mm
) without ferrule
2
14 AWG (2.5 mm
...
in (10...17 mm)
25 / 64
43 / 64
PVC or other material that is serviceable for
outdoor, UV-protected and suitable for use in
underground ducts
Specification
442.5...663.8 lbf-in (50...75 Nm)
292...389 lbf-in (33...44 Nm)
11.5 lbf-in (1.3 Nm)
177 lbf-in (20 Nm)
) with ferrule