Use local regulations and datasheet of the manufacturer to determine the cable diameter for
the DC power cables. Recommended cable for the 450 kW system is 185 mm
(with a reinforced isolation > 5400 V DC) for a distance until 492.13 ft.

4.4.5. Cables between the Power Cabinets

The following cables are not in the scope of supply of ABB.
1x GND cable;
1x Interlock cable;
1x CAN cable.
For detailed information about type of glass fiber cable which are needed,
see Communication glass fiber cable on Page 21.
For the overview of the grounding of the system, see Appendix J Ground
overview of the system on Page 127.

4.4.6. Cable specification list

Tables below provides general specifications for the needed cables. Use these tables to
select cables, taking into account local installation conditions, cable length, cable
temperature rating, losses and local regulations.
AC and DC power cables
Functional description
Number of cores
Cross section
Min – Max external
diameter to fit through
gland
Shielding
Conductor
Insulation
Nominal Voltage Uo/U
Test Voltage
Ambient Temperature
range
Core identification
Revision: 1.2
Date released: 16-08-2018
DC Power cable
1
350 – 600 MCM
1.06 – 1.38 Inch
No
Tinned copper or
aluminum conductor, fine
wire
stranded acc. to VDE
0295 cl.5/IEC Cl.5
Special rubber or PVC
(outdoor use, UV-
protected, oil resistant)
600/1000 Vac
900/1500 Vdc
6 kV
-40ºC to 105ºC,
permissible conductor
operating
temperature +90°C
NOTICE
PE cable
1
2 AWG
0.51 – 0.83 Inch
No
Fine strand copper wire
acc. to VDE 0295 Cl. 5/
IEC 60228 Cl. 5
Special PVC (outdoor
use, UV-protected, oil
resistant)
600 Vac
4 kV
-40ºC to 105ºC
gn/ye or gn
2
(= 350 MCM)
AC utility power cable
4
14 AWG
0.20 – 0.39 Inch
No
Bare copper, fine wired,
bunch stranded acc. to
VDE 0295 Cl.5/IEC Cl.5
Special PVC (outdoor
use, UV-protected, oil
resistant)
600 Vac
4 kV
-40ºC to 105ºC
Color for US Acc. to US
National Electrical Code
and for Canada Acc. to
the CEC (Canadian
Electric Code)
COMPANY CONFIDENTIAL