ABB AC500 PLC Hardware Manual page 810

Table of Contents

Advertisement

Device Specifications
Communication Interface Modules (S500) > CS31
Parameter
Connection of the channels AO0+...AO1+
Reference potential for AO0+ to AO1+
Output type
Electrical isolation
Configurability
Output resistance (load),
as current output
Output loadability,
as voltage output
Indication of the output signals
Resolution
Conversion error of the analog values caused
by non-linearity, adjustment error at factory and
resolution within the normal range
Relationship between input signal and hex
code
Unused outputs
1.7.2.2.13
Ordering Data
Part No.
1SAP 221 200 R0001 CI592-CS31, CS31 bus module with
1SAP 421 200 R0001 CI592-CS31-XC, CS31 bus module
1.7.2.3
DC551-CS31 - Digital Inputs and Output
8 digital inputs 24 VDC, 16 configurable digital inputs/outputs
Module-wise electrically isolated
Fast counter
XC version for usage in extreme ambient conditions available
810
Unipolar
Bipolar
Description
8 DI, 8 DC, 4 AI, 2 AO
with 8 DI, 8 DC, 4 AI, 2 AO,
XC version
*) For planning and commissioning of new installations use modules in Active
status only.
3ADR010121, 13, en_US
Value
Terminals 3.5 and 3.6
Terminal 3.7 (AO-) for voltage output
Terminals 1.9, 2.9, 3.9 and 4.9 for current
output
Current
Voltage
Against internal supply and other modules
-10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually)
0 W...500 W
±10 mA max.
1 LED per channel (brightness depends on
the value of the analog signal)
12 bits (+ sign)
Typ. 0.5 %, max. 1 %
Table Output Ranges Voltage and Current
Ä Chapter 1.7.2.2.11.3 "Output Ranges
Voltage and Current" on page 804
Are configured as "unused" (default value)
and can be left open-circuited