Device Specifications
Communication Interface Modules (S500) > PROFINET
Technical Data of the Analog Inputs
Parameter
Number of channels per module
Distribution of channels into groups
Connection if channels AI0+ to AI3+
Reference potential for AI0+ to AI3+
Input type
Electrical isolation
Configurability
Channel input resistance
Time constant of the input filter
Indication of the input signals
Conversion cycle
Resolution
Conversion error of the analog values
caused by non-linearity, adjustment error at
factory and resolution within the normal
range
Relationship between input signal and hex
code
Unused inputs
Overvoltage protection
Technical Data of the Analog Inputs, if used as Digital Inputs
Parameter
Number of channels per module
Distribution of channels into groups
Connections of the channels AI0+ to AI3+
1044
Unipolar
Bipolar
3ADR010121, 13, en_US
Value
4
1 group with 4 channels
Terminals 1.0 to1.3
Terminal 1.4 (AI-) for voltage and RTD meas-
urement
Terminal 1.9, 2.9 and 3.9 for current measure-
ment
Voltage 0 V... 10 V, current or Pt100/Pt1000/
Ni1000
Voltage -10 V... +10 V
Against Ethernet network
0 V...10 V, -10 V...+10 V, 0 mA...20 mA, 4
mA...20 mA Pt100/1000, Ni1000 (each input
can be configured individually)
Voltage: > 100 kW
Current: ca. 330 W
Voltage: 100 µs
Current: 100 µs
1 LED per channel (brightness depends on the
value of the analog signal)
1 ms (for 4 inputs + 2 outputs); with RTDs Pt/
Ni... 1 s
Range 0 V...10 V: 12 bits
Range -10 V...+10 V: 12 bits + sign
Range 0 mA...20 mA: 12 bits
Range 4 mA...20 mA: 12 bits
Range RTD (Pt100, PT1000, Ni1000): 0.1 °C
Typ. 0.5 %, max. 1 %
Tables Input ranges voltage, current and digital
input and Input range resistor
Are configured as "unused" (default value)
Yes
Value
Max. 4
1 group of 4 channels
Terminals 1.0 to 1.3
2019/04/17