System Assembly, Construction and Connection
AC500-eCo > Handling of Accessories
8.
Technical Data
Parameter
RTC accuracy (at 25 °C)
Ordering Data
Part No.
1SAP 181 500 R0001
1TNE 968 901 R5210
2.5.5.7
CR2032 - Battery for Real-Time Clock
Intended Pur-
A standard lithium battery (type CR2032) is used to backup the real-time clock (RTC) in the
pose
adaptors TA561-RTC
and TA562-RS-RTC
and Real-time Clock " on page 1233 during power failures.
The CPU monitors the discharge degree of the battery. An diagnoses message is output before
the battery condition becomes critical (about 2 weeks before). After the diagnosis message has
appeared, the battery should be replaced as soon as possible.
Handling
The handling instructions of the battery manufacturer must be observed.
Instruction
The Material Safety Data Sheet (MSDS) of the battery manufacturer must be observed.
Do not short-circuit or re-charge the battery! It can cause excessive heating and explosion.
Do not disassemble the battery!
Do not heat up the battery and not put into fire! Risk of explosion.
1240
Only now the CPU can connected to power.
Set the time of the real-time clock.
*) For planning and commissioning of new installations use modules in Active
status only.
Ä Chapter 2.5.5.3 "TA561-RTC - Real-time Clock Adaptor " on page 1225
Ä Chapter 2.5.5.6 "TA562-RS-RTC - Adaptor with Serial RS-485 (COM2)
3ADR010121, 13, en_US
Value
Typ. ±2 s / 24 h
Description
TA562-RS-RTC, serial
RS-485 and real-time clock
adaptor for PM55x-xP and
PM56x-xP
TA562-RS-RTC, serial
RS-485 and real-time clock
adaptor for PM55x-xP and
PM56x-xP, lithium battery
included (available in China
only)
Product Life Cycle Phase *)
Active
Active
2019/04/17