Parameter
Input data length
Output data length
Max. power dissipation within the module
Setting of the I/O device identifier
Operation and error displays
Weight (without terminal unit)
Mounting position
Cooling
Electrical isolation
Diagnosis
Parameter
Bus connection
Switch
Technology
Transfer rate
Transfer method
Ethernet
Expandability
2019/04/17
Rated protection fuse on UP
Inrush current from UP (at power up)
Current consumption via UP (normal
operation)
Connections
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
3ADR010121, 13, en_US
Communication Interface Modules (S500) > PROFINET
Value
10 A fast
On request
0.15 A
Terminals 1.0, 2.0 and 3.0 for +24 V (UP)
Terminals 1.1, 2.1 and 3.1 for 0 V (ZP)
0...36 bytes
0...36 bytes
5 W
With 2 rotary switches at the front side of the
module
18 LEDs (total)
ca. 125 g
Horizontal or vertical
The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
Ethernet interface against the rest of the
module, each serial and CAN port against each
other and the rest of the module
Ä Chapter 1.7.6.5.8 "Diagnosis"
See Diagnosis
on page 1095
Value
2 x RJ45
Integrated
Hilscher netX100
10/100 Mbit/s (full-duplex)
According to Ethernet II, IEE802.3
100 base-TX, internal switch, 2x RJ45 socket
Max. 10 S500 I/O modules