Device Specifications
Communication Interface Modules (S500) > PROFINET
1.7.6.3.2
Functionality
The CI502 Bus Module contains 24 I/O channels with the following properties:
8 digital configurable inputs/outputs
8 digital inputs: 24 VDC
8 digital outputs: 24 VDC, 0.5 A max.
The inputs/outputs are electrically isolated from the Ethernet network. There is no potential sep-
aration between the channels. The configuration of the analog inputs/outputs is performed by
software.
Parameter
Interface
Protocol
Power supply
Supply of the electronic circuitry of the I/O
expansion modules attached
Rotary switches
Configurable digital inputs/outputs
Digital inputs
Digital outputs
LED displays
External supply voltage
Effect of incorrect input terminal connection
Required terminal unit
1.7.6.3.3
Electrical Connection
The Ethernet bus module CI502-PNIO is plugged on the I/O terminal unit TU507-ETH
Ä Chapter 1.4.1 "TU507-ETH and TU508-ETH for Ethernet Communication Interface Modules"
on page 145 or TU508-ETH
munication Interface Modules" on page 145. Properly seat the module and press until it locks in
place. The terminal unit is mounted on a DIN rail or with 2 screws plus the additional accessory
for wall mounting (TA526
The electrical connection of the I/O channels is carried out using the 30 terminals of the I/O ter-
minal unit. I/O modules can be replaced without re-wiring the terminal units.
The terminals 1.8 and 2.8 as well as 1.9, 2.9 and 3.9 are electrically interconnected within the
terminal unit and have always the same assignment, independent of the inserted module:
Terminals 1.8 and 2.8: Process supply voltage UP = +24 VDC
1048
Ä Chapter 1.4.1 "TU507-ETH and TU508-ETH for Ethernet Com-
Ä Chapter 1.8.2.4 "TA526 - Wall Mounting Accessory" on page 1152).
For a detailed description of the mounting, disassembly and electrical connec-
tion of the module, please refer to the System Assembly, Construction and Con-
Ä Chapter 2.6 "AC500 (Standard)" on page 1248.
nection chapter
3ADR010121, 13, en_US
Value
Ethernet
PROFINET IO RT
From the process supply voltage UP
Through the expansion bus interface (I/O bus)
For setting the IO device identifier for configura-
tion purposes (00h to FFh)
8 (configurable via software)
8 (24 VDC; delay time configurable via soft-
ware)
8 (24 VDC, 0.5 A max.)
For system displays, signal states, errors and
power supply
Via terminals ZP, UP and UP3 (process supply
voltage 24 VDC)
Wrong or no signal detected, no damage up to
35 V
TU507-ETH or TU508-ETH
"TU507-ETH and TU508-ETH for Ethernet
Communication Interface Modules"
on page 145
Ä Chapter 1.4.1
2019/04/17