ABB AC500 PLC Hardware Manual page 1042

Table of Contents

Advertisement

Device Specifications
Communication Interface Modules (S500) > PROFINET
Parameter
Acyclic services
Supported alarm types
Min. bus cycle
Conformance class
Protective functions (according to IEC
61131-3)
*) Priorization with the aid of VLAN-ID including priority level
Technical Data of the Digital Inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels DI0 to DI7
Reference potential for all inputs
Indication of the input signals
Input type (according EN 61131-2)
Input delay (0->1 or 1->0)
Input signal voltage
Ripple with signal 0
Ripple with signal 1
Input current per channel
Max. cable length
1042
0-Signal
Undefined Signal
1-Signal
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
Shielded
Unshielded
3ADR010121, 13, en_US
Value
PNIO read / write sequence (max. 1024 bytes
per telegram)
Process-Alarm service
Process Alarm, Diagnostic Alarm, Return of
SubModule, Plug Alarm, Pull Alarm
1 ms
CC A
Protected against:
short circuit
reverse supply
overvoltage
reverse polarity
Electrical isolation from the rest of the module
Value
8
1 group of 8 channels
Terminals 2.0 to 2.7
Terminals 1.9...3.9 (Minus pole of the supply
voltage, signal name ZP)
1 yellow LED per channel, the LED is ON when
the input signal is high (signal 1)
Type 1
Typ. 0.1 ms, configurable from 0.1...32 ms
24 VDC
-3 V...+5 V
> +5 V...< +15 V
+15 V...+30 V
Within -3 V...+5 V
Within +15 V...+30 V
Typ. 5 mA
> 1 mA
> 2 mA
< 8 mA
1000 m
600 m
2019/04/17