ABB AC500 PLC Hardware Manual page 739

Table of Contents

Advertisement

The inputs/outputs are electrically isolated from the CANopen network. There is no potential
separation between the channels. The configuration of the analog inputs/outputs is performed
by software.
For use in extreme ambient conditions (e.g. wider temperature and humidity range), a special
XC version of the device is available.
1.7.1.3.2
Functionality
Parameter
Interface
Protocol
Power supply
Supply of the electronic circuitry of the I/O
modules attached
Rotary switches
LED displays
External supply voltage
Transmission rates
Bus connection
Processor
Expandability
State display
Adjusting elements
Ambient temperature
Current consumption
Weight (without terminal unit)
Process supply voltages UP/UP3
2019/04/17
Rated value
Max. load for the terminals
Protection against reversed voltage
Rated protection fuse on UP/UP3
Galvanic isolation
Inrush current from UP (at power up)
Current consumption via UP (normal
operation)
Current consumption via UP3
3ADR010121, 13, en_US
Communication Interface Modules (S500) > CANopen
Value
CAN
CANopen
From the process supply voltage UP
Through the expansion bus interface (I/O bus)
For setting the CANopen Node ID for configura-
tion purposes (00h to FFh)
For system displays, signal states, errors and
power supply
Via terminals ZP, UP and UP3 (process supply
voltage 24 VDC)
10 / 20 / 50 / 125 / 250 / 500 / 800 kbit/s 1
Mbit/s Auto baudrate detection is supported
Depending on used terminal unit TU510: 9-pin
D-sub connector TU518: 10-pin terminal block
Hilscher netX100
Max. 10 S500 I/O modules
Module state: PWR/RUN, CN-RUN, CN-ERR,
E-ERR, I/O bus
2 rotary switches for generation of the node
address
Ä Chapter 2.6.1 "System
System data AC500
Data AC500" on page 1248
System data AC500 XC
"System Data AC500-XC" on page 1309
UP: 0.2 A UP3: 0.06 A + 0.5 A max. per output
Ca. 125 g
24 VDC (for inputs and outputs)
10 A
Yes
10 A fast
CANopen interface against the rest of the
module
On request
0.2 A
0.06 A + 0.5 A max. per output
Device Specifications
Ä Chapter 2.7.1
739