With 3-wire configuration, 2 adjacent analog channels belong together (e. g. the channels 0 and
1). In this case, both channels are configured according to the desired operating mode. The
lower address must be the even address (channel 0), the next higher address must be the odd
address (channel 1).
The constant current of one channel flows through the resistance thermometer. The constant
current of the other channel flows through one of the cores. The module calculates the meas-
ured value from the two voltage drops and stores it under the input with the higher channel
number (e. g. I1).
In order to keep measuring errors as small as possible, it is necessary to have all the involved
conductors in the same cable. All the conductors must have the same cross section.
The following measuring ranges can be configured
on page 1024 :
Pt100
Pt100
Pt1000
Ni1000
The function of the LEDs is described under Diagnosis and displays / Displays
1.7.6.2.8 "Diagnosis and State LEDs" on page 1030.
The module CI501-PNIO performs a linearization of the resistance characteristic.
To avoid error messages from unused analog input channels, configure them as "unused".
2019/04/17
Communication Interface Modules (S500) > PROFINET
Ä Chapter 1.7.6.2.7 "Parameterization"
-50 °C...+70 °C
-50 °C...+400 °C
-50 °C...+400 °C
-50 °C...+150 °C
3ADR010121, 13, en_US
Device Specifications
3-wire configuration, 2 chan-
nels used
3-wire configuration, 2 chan-
nels used
3-wire configuration, 2 chan-
nels used
3-wire configuration, 2 chan-
nels used
Ä Chapter
1015

Advertisement

Chapters

Table of Contents
loading

Table of Contents