Device Specifications
Communication Interface Modules (S500) > PROFIBUS
Parameter
Reference potential for all inputs
Indication of the input signals
Input type (according EN 61131-2)
Input delay (0->1 or 1->0)
Input signal voltage
Ripple with signal 0
Ripple with signal 1
Input current per channel
Max. cable length
Technical Data of the Digital Outputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels DO0 to DO7
Reference potential for all outputs
Common power supply voltage
Output voltage for signal 1
Output delay (0->1 or 1->0)
Output current
Leakage current with signal 0
Demagnetization with inductive DC load
Output switching frequency
1000
Signal 0
Undefined Signal
Signal 1
Input voltage +24 V
Input voltage +5 V
Input voltage +15 V
Input voltage +30 V
Shielded
Unshielded
Rated value per channel
Max. value (all channels together)
Fuse for UP3
With resistive load
3ADR010121, 13, en_US
Value
Terminals 2.9 ... 4.9 (Minus pole of the supply
voltage, signal name ZP)
1 yellow LED per channel, the LED is ON when
the input signal is high (signal 1)
Type 1
Typ. 0.1 ms, configurable from 0.1...32 ms
24 VDC
-3 V...+5 V
> +5 V...< +15 V
+15 V...+30 V
Within -3 V...+5 V
Within +15 V...+30 V
Typ. 5 mA
> 1 mA
> 2 mA
< 8 mA
1000 m
600 m
Value
8
1 group of 8 channels
Terminals 4.0 to 4.7
Terminals 2.9 ... 4.9 (minus pole of the supply
voltage, signal name ZP)
For all outputs terminal 4.8 (plus pole of the
supply voltage, signal name UP3)
UP3 (-0.8 V)
On request
500 mA at UP3 = 24 V
4 A
< 0.5 mA
10 A fast
Via internal varistors (see figure below this
table)
On request