Details about configuration are described in Parameterization.
1.7.5.2.7
Parameterization
Parameters of the Module
Name
Module ID
Parameter length Internal
Reserved (1
byte)
Error LED / Fail-
safe function
Ä Table 162 "Set
tings "Error LED /
Failsafe func-
tion""
on page 991
(see table )
Reserved (20
bytes)
Check supply
Fast counter
1
) With a faulty ID, the module reports a "parameter error" and does not perform cyclic process
data transmission.
2
) Counter operating modes, see Fast Counter
on page 394.
Table 162: Settings "Error LED / Failsafe function"
Setting
On
Off by E4
Off by E3
On + Failsafe
Off by E4 + Failsafe
Off by E3 + Failsafe
*) The parameter Behaviour DO at comm. error is only analyzed if the Failsafe mode is ON.
2019/04/17
Value
Internal
1
)
0
On
Off by E4
Off by E3
On + failsafe
Off by E4 + fail-
safe
Off by E3 + fail-
safe
0
On
Off
0
:
2
10
)
3ADR010121, 13, en_US
Communication Interface Modules (S500) > PROFIBUS
Internal value
Internal value,
type
0x1C25
WORD
31
BYTE
0
BYTE
0
BYTE
1
2
16
17
18
0
BYTE
0
BYTE
1
0
BYTE
:
10
Ä Chapter 1.5.1.2.10 "Fast Counter"
Description
Error LED (S-ERR) lights up at errors of all
error classes, Failsafe mode off
Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe mode off
Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe mode off
Error LED (S-ERR) lights up at errors of all
error classes, Failsafe mode on *)
Error LED (S-ERR) lights up at errors of error
classes E1, E2 and E3, Failsafe mode on *)
Error LED (S-ERR) lights up at errors of error
classes E1 and E2, Failsafe mode on *)
Device Specifications
Default
0x1C25
31
0
0
0
1
0
991