ABB AC500 PLC Hardware Manual page 1196

Table of Contents

Advertisement

System Assembly, Construction and Connection
AC500-eCo > Mechanical Dimensions
2.5.1.6
Mechanical Data
Parameter
Mounting
Degree of protection
Housing
Vibration resistance acc. to EN 61131-2
Shock test
Mounting of the modules:
DIN rail according to DIN EN 50022
Mounting with screws
Fastening torque
2.5.1.7
Approvals and certifications
Information on approvals and certificates can be found in the corresponding chapter of the
Main catalog, PLC Automation.
2.5.2 Mechanical Dimensions
2.5.2.1
Switchgear Cabinet Assembly
PLC enclosure
To protect PLCs against:
unauthorized access,
dusting and pollution,
moisture and wetness and
mechanical damage,
switchgear cabinet IP54 for common dry factory floor environment is suitable.
1196
Information on EMC-conforming assembly and construction is provided within
the overall functions section
Construction" on page 1186.
NOTICE!
PLC damage due to wrong enclosures
Due to their construction (degree of protection IP 20 according to EN 60529)
and their connection technology, the devices are suitable only for operation in
enclosed switchgear cabinets.
3ADR010121, 13, en_US
Value
Horizontal
IP 20 (if all terminal screws are tightened)
Classification V-2 according to UL 94
all three axes (DIN rail mounting)
5 Hz...8.4 Hz, continuous 3.5 mm
8.4 Hz...150 Hz, continuous 1 g
All three axes
15 g, 11 ms, half-sinusoidal
35 mm, depth 7.5 mm or 15 mm
Screws with a diameter of 4 mm
1.2 Nm
Ä Chapter 2.4.4 "EMC-Conforming Assembly and
2019/04/17