ABB AC500 PLC Hardware Manual page 465

Table of Contents

Advertisement

Interna
l value
2
3
4
5
8
9
10
11
14
15
16
17
18
19
Table 59: Channel Monitoring
Intern
al
value
0
1
2
3
2019/04/17
Operating modes of the analog inputs, individually configurable
Digital input
Analog input 0 mA...20 mA
Analog input 4 mA...20 mA
Analog input -10 V...+10 V
Analog input Pt100, -50 °C...+400 °C (2-wire)
Analog input Pt100, -50 °C...+400 °C (3-wire), requires 2 channels *)
Analog input 0...10 V via differential inputs, requires 2 channels *)
Analog input -10 V...+10 V via differential inputs, requires 2 channels *)
Analog input Pt100, -50 °C...+70 °C (2-wire)
Analog input Pt100, -50 °C...+70 °C (3-wire), requires 2 channels *)
Analog input Pt1000, -50 °C...+400 °C (2-wire)
Analog input Pt1000, -50 °C...+400 °C (3-wire), requires 2 channels *)
Analog input Ni1000, -50 °C...+150 °C (2-wire)
Analog input Ni1000, -50 °C...+150 °C (3-wire), requires 2 channels *)
*) In the operating modes with 3-wire configuration or with differential inputs, two
adjacent analog inputs belong together (e.g. the channels 0 and 1). In these cases,
both channels are configured in the desired operating mode. The lower address must
be the even address (channel 0). The next higher address must be the odd address
(channel 1). The converted analog value is available at the higher address (channel
1).
4
)
Monitoring
Plausibility, open-circuit (broken wire) and short circuit
5
)
Open-circuit and short circuit
Plausibility
No monitoring
3ADR010121, 13, en_US
Device Specifications
I/O Modules > Analog I/O Modules
465