ABB AC500 PLC Hardware Manual page 1030

Table of Contents

Advertisement

Device Specifications
Communication Interface Modules (S500) > PROFINET
Name
Behaviour DO at
comm. error
Substitute value
at output
Detect voltage
overflow at out-
puts
1
) The parameters Behaviour DO at comm. error is only analyzed if the Failsafe-mode is ON.
2
) The state "externally voltage detected" appears, if the output of a channel DC0...DC7 should
be switched on while an externally voltage is connected
nection" on page 1008. In this case the start up is disabled, as long as the externally voltage is
connected. The monitoring of this state and the resulting diagnosis message can be disabled
by setting the parameters to "OFF".
1.7.6.2.8
Diagnosis and State LEDs
Structure of the Diagnosis Block via PNIO_DEV_ALARM Function Block
Byte Number
1
2
3
1030
Value
Off
1
)
Last value
Last value 5 sec
Last value 10 sec
Substitute value
Substitute value
5 sec
Substitute value
10 sec
0...255
Off
On
2
)
Description
Diagnosis Byte, slot number
Diagnosis Byte, module
number
Diagnosis Byte, channel
3ADR010121, 13, en_US
Internal value
Internal value,
type
0
BYTE
1
6
11
2
7
12
00h...FFh
BYTE
0
BYTE
1
Ä Chapter 1.7.6.2.3 "Electrical Con-
Possible Values
31 = CI501-PNIO (e. g. error at inte-
grated 8 DI / 8 DO)
1 = 1st connected S500 I/O module
...
10 = 10th connected S500 I/O module
According to the I/O bus specification
passed on by modules to the fieldbus
master
According to the I/O bus specification
passed on by modules to the fieldbus
master
Default
Off
0x00
0
0x0000
On
0x01
2019/04/17