1.7.6.5.4
Assignment of the Ethernet Ports
The terminal unit for the communication interface module provides two Ethernet interfaces with
the following pin assignment:
Table 189: Pin assignment RJ45 jack:
Interface
1.7.6.5.5
Addressing
1.7.6.5.6
I/O Configuration
The CI506-PNIO stores some PROFINET configuration parameters:
●
Slave station name
●
Slave station type
●
IP address configuration
●
MAC address
●
Production data
No more configuration data is stored. The serial interfaces and the CANopen interface is config-
ured via software. For details, refer to Parameterization
on page 1090.
2019/04/17
Pin
1
2
3
4
5
6
7
8
Shield
For further information regarding wiring and cable types see chapter Ethernet
Ä Chapter 2.6.4.10 "Ethernet Connection Details" on page 1288.
The module reads the position of the rotary switches only during power-up, i. e.
changes of the switch position during operation will have no effect until the next
module initialization.
3ADR010121, 13, en_US
Communication Interface Modules (S500) > PROFINET
Signal
Description
TxD+
Transmit data +
TxD-
Transmit data -
RxD+
Receive data +
NC
not used
NC
not used
RxD-
Receive data -
NC
not used
NC
not used
Cable shield
Functional earth
Ä Chapter 1.7.6.5.7 "Parameterization"
Device Specifications
1089