Device Specifications
Function Modules > S500
Parameter
Output current
Switching frequency
Short-circuit-proof / overload-proof
Overload message (I > 0.1x A)
Output current limitation
Resistance to feedback against 24V signals
Resistance to feedback against reverse
polarity
Max. cable length (shielded)
Technical Data
Parameter
of the 5 V
Number of supplies
Sensor Supply
Voltage supply (outputs unloaded)
Resistance to feedback against reverse
polarity
Output current
Output diagnosis
Technical Data
Parameter
of the 0 V Refer-
Number of reference inputs (internally con-
ence Input
nected to ZP through internal fuse)
Max. current per connection
Internal fuse protection
1.6.2.1.10
Ordering Data
Part No.
1SAP 260 300 R0001 CD522, encoder & PWM module,
1SAP 460 300 R0001 CD522-XC, encoder & PWM module,
674
Terminals 1.4 and 1.6
Terminals 3.4 to 3.7
Description
2 encoder inputs, 2 PWM outputs,
2 digital inputs 24 VDC, 8 digital
outputs 24 VDC
2 encoder inputs, 2 PWM outputs,
2 digital inputs 24 VDC, 8 digital
outputs 24 VDC, XC version
*) For planning and commissioning of new installations use modules in Active
status only.
3ADR010121, 13, en_US
Value
≤ 10 mA
< 1 Mhz (depending on firmware)
Yes
Yes, after ca. 100 ms
Yes, automatic reactivation after short-circuit/
overload
Yes
No
100 m
Value
2, independently configuration
5 VDC +/- 5%
No
100 mA max. (independently)
200 mA max. (parallel use)
Yes, with diagnosis LED and error message
Value
6
0.5 A
2 A
2 A
Product Life Cycle Phase *)
Active
Active
2019/04/17