ABB AC500 PLC Hardware Manual page 999

Table of Contents

Advertisement

Parameter
Max. power dissipation within the module
Number of digital inputs
Number of digital outputs
Number of analog inputs
Number of analog outputs
Reference potential for all digital inputs and
outputs
Setting of the PROFIBUS DP identifier
Diagnose
Operation and error displays
Weight (without terminal unit)
Mounting position
Cooling
Technical Data of the Digital Inputs
Parameter
Number of channels per module
Distribution of the channels into groups
Terminals of the channels DI0 to DI7
2019/04/17
Current consumption via UP (normal
operation)
Current consumption via UP3
Connections
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
3ADR010121, 13, en_US
Communication Interface Modules (S500) > PROFIBUS
Value
0.2 A
0.06 A + 0.5 A max. per output
Terminals 2.8 and 3.8 for +24 V (UP)
Terminal 4.8 for +24 V (UP3)
Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)
6 W
8
8
4
2
Minus pole of the supply voltage, signal name
ZP
With 2 rotary switches at the front side of the
module
See Diagnosis
Ä Chapter 1.7.5.2.8 "Diagnosis"
on page 992
34 LEDs (totally)
Ca. 125 g
Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
Value
8
1 group of 8 channels
Terminals 3.0 to 3.7
Device Specifications
999