All values are validated during the parameterization of the CI504-PNIO according to the
appended expansion modules. In the case of error, a diagnostic message "parameter errors" is
generated and the cyclic process data transfer is terminated.
Parameters of the 3 Serial Channels
Name
Behavior for serial channel
communication during PRO-
FINET communication fault
Number of frames/data blocks
in reception FIFO
Number of frames/Data blocks
in transmission FIFO
Behavior during reception
FIFO overflow
Physical layer
RTS control
TLS (RTS leading cycle)
CDLY (RTS trailing cycle)
Character timeout
Telegram ending selection
2019/04/17
Communication Interface Modules (S500) > PROFINET
Value
Internal
value
Stop communi-
0
cation and
reset FIFO
Continue serial
1
communication
1...40
1...40
1...40
1...40
Discard new
1
received
frames
Overwrite
2
oldest frame in
FIFO
Discard new
3
received
frames and
send PRO-
FINET alarm
Overwrite
4
oldest frame in
FIFO and send
PROFINET
alarm
RS232
1
RS485
2
RS422
3
None
0
Telegram
1
RTS/CTS
2
(DTE <-> DTE)
RTS/CTS
3
(DTE -> DCE)
RTS/CTS
4
(DCE <- DTE)
0...850 ms
0...850
0...850 ms
0...850
0/32 bits
0/32
None
0
String (check
1
reception)
3ADR010121, 13, en_US
Device Specifications
Internal
Default
value, type
BYTE
0
BYTE
1
BYTE
1
BYTE
2
BYTE
1
BYTE
1
WORD
0
WORD
0
WORD
0
BYTE
None
1075