ABB AC500 PLC Hardware Manual page 1312

Table of Contents

Advertisement

System Assembly, Construction and Connection
AC500-XC > System Data AC500-XC
Parameter
Influence of line-conducted interferences
Influence of power frequency magnetic fields
2.7.1.2
Mechanical Data
Parameter
Wiring method
Degree of protection
Vibration resistance
Shock resistance
Assembly position
Assembly on DIN rail
DIN rail type
Assembly with screws
Screw diameter
Fastening torque
1312
In order to prevent malfunctions, it is recommended, that the operating per-
sonnel discharge themselves prior to touching communication connectors or
perform other suitable measures to reduce effects of electrostatic discharges.
NOTICE!
Risk of malfunctions!
Unused slots for communication modules are not protected against accidental
physical contact.
Unused slots for communication modules must be covered with dummy
communication modules (TA524
munication Module" on page 1304 to achieve IP20 rating.
I/O bus connectors must not be touched during operation.
3ADR010121, 13, en_US
Value
Yes, according to:
IEC 61000-4-6, zone B,
criterion A
Yes, according to:
IEC 61000-4-8, zone B,
criterion A
Ä Chapter 2.6.5.4 "TA524 - Dummy Com-
Value
Spring terminals
IP 20
Yes, according to:
IEC 61131-2
IEC 60068-2-6
IEC 60068-2-64
Yes, according to:
IEC 60068-2-27
Horizontal
Vertical (no application in salt mist environ-
ment)
According to IEC 60715
35 mm, depth 7.5 mm or 15 mm
4 mm
1.2 Nm
2019/04/17