Parameter
Reference potential for all digital inputs and
outputs
Setting of the IO device identifier
Diagnose
Operation and error displays
Weight (without terminal unit)
Mounting position
Extended ambient temperature (XC version)
Cooling
Parameter
Bus connection
Switch
Technology
Transfer rate
Transfer method
Ethernet
Expandability
Adjusting elements
Supported protocols
2019/04/17
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
3ADR010121, 13, en_US
Communication Interface Modules (S500) > PROFINET
Value
Minus pole of the supply voltage, signal name
ZP
With 2 rotary switches at the front side of the
module
See Diagnosis and Displays
1.7.6.2.8 "Diagnosis and State LEDs"
on page 1030
32 LEDs (totally)
Ca. 125 g
Horizontal or vertical with derating (output load
reduced to 50 % at 40 °C per group)
>60 °C on request
The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
Value
2 x RJ45
Integrated
Hilscher netX100
10/100 Mbit/s (full-duplex)
According to Ethernet II, IEE802.3
100 base-TX, internal switch, 2x RJ45 socket
Max. 10 S500 I/O modules
2 rotary switches for generation of an explicit
name
RTC - real time cyclic protocol, class 1 *)
RTA - real time acyclic protocol
DCP - discovery and configuration protocol
CL-RPC - connectionless remote procedure
Call
LLDP - link layer discovery protocol
MRP - MRP Client
Device Specifications
Ä Chapter
1041