ABB AC500 PLC Hardware Manual page 1252

Table of Contents

Advertisement

System Assembly, Construction and Connection
AC500 (Standard) > Mechanical Dimensions
Electromagnetic Compatibility
High energy surges
Radiation (radio disturbance)
1
) High requirement for shipping classes are achieved with additional specific measures (see
specific documentation).
²) CM = Common Mode, DM = Differential Mode
2.6.1.6
Mechanical Data
Parameter
Mounting
Degree of protection
Housing
Vibration resistance acc. to EN 61131-2
Shock test
Mounting of the modules:
DIN rail according to DIN EN 50022
Mounting with screws
Fastening torque
2.6.1.7
Approvals and certifications
Information on approvals and certificates can be found in the corresponding chapter of the
Main catalog, PLC Automation.
2.6.2 Mechanical Dimensions
2.6.2.1
Switchgear Cabinet Assembly
1252
Test voltage
Power supply DC
DC I/O supply
Communication Lines, shielded
AC I/O unshielded
I/O analog, I/O DC unshielded
Information on EMC-conforming assembly and construction is provided within
the overall functions section
Construction" on page 1186.
3ADR010121, 13, en_US
3V zone B, 10 V is also met.
According to IEC 61000-4-5, zone B,
criterion B
1 kV CM / 0.5 kV DM ²)
0.5 kV CM / 0.5 kV DM ²)
1 kV CM ²)
2 kV CM / 1 kV DM ²)
1 kV CM / 0.5 kV DM ²)
According to IEC 55011, group 1, class
A
Value
Horizontal
IP 20
Classification V-2 according to UL 94
all three axes
2 Hz...8.4 Hz, continuous 3.5 mm
8.4 Hz...150 Hz, continuous 1 g (higher values
on request)
All three axes
15 g, 11 ms, half-sinusoidal
35 mm, depth 7.5 mm or 15 mm
Screws with a diameter of 4 mm
1.2 Nm
Ä Chapter 2.4.4 "EMC-Conforming Assembly and
2019/04/17