ABB AC500 PLC Hardware Manual page 1193

Table of Contents

Advertisement

Parameter
Parameter
Temperature
Humidity
Air pressure
2.5.1.2
Creepage Distances and Clearances
The creepage distances and clearances meet the requirements of the overvoltage category II,
pollution degree 2.
2.5.1.3
Insulation Test Voltages, Routine Test
According to EN
Parameter
61131-2
200 V...240 V circuits against
other circuitry
100 V...127 V circuits against
other circuitry
100 V...240 V circuits against
other circuitry
24 V circuits (supply, 24 V
inputs/outputs, analogue
inputs/outputs ), if they are
electrically isolated against
other circuitry
COM interfaces, electrically
isolated
2019/04/17
DC supply
AC supply
NOTICE!
Exceeding the maximum power supply voltage (> 30 VDC) for process or
supply voltages could lead to unrecoverable damage of the system. The system
could be destroyed.
Operating
Storage
Transport
Operating
Storage
3ADR010121, 13, en_US
Value
Interruption < 10 ms, time between 2 interruptions
> 1 s, PS2
Interruption < 0.5 periods, time between 2 inter-
ruptions > 1 s
Value
0 °C...+60 °C (horizontal mounting of modules)
0 °C...+40 °C (vertical mounting of modules and
output load reduced to 50 % per group)
-40 °C...+70 °C
-40 °C...+70 °C
Max. 95 %, without condensation
> 800 hPa / < 2000 m
> 660 hPa / < 3500 m
Value
2500 V
1500 V
2500 V
500 V
500 V
System Assembly, Construction and Connection
AC500-eCo > System Data AC500-eCo
1.2/50 µs
1.2/50 µs
1.2/50 µs
1.2/50 µs
1.2/50 µs
1193