ABB AC500 PLC Hardware Manual page 1029

Table of Contents

Advertisement

Table 169: Channel Configuration
Internal value
0 (default)
128
129
130
Table 170: Channel Monitoring
Internal value
0
3
Table 171: Substitute Value
Intended behaviour of
output channel when the
control system stops
Output OFF
Last value infinite
Last value for 5 s and then
turn off
Last value for 10 s and then
turn off
Substitute value infinite
Substitute value for 5 s and
then turn off
Substitute value for 10 s and
then turn off
Group Parameters for the Digital Part
Name
Input delay
Detect short cir-
cuit at outputs
2019/04/17
Operating modes of the analog outputs, individually configu-
rable
Not used
-10 V...+10 V
0 mA...20 mA
4 mA...20 mA
Check channel
Plausib(ility), cut wire, short circuit
None
Required setting of the
module parameter "Behav-
iour of outputs in case of a
communication error"
Off
Last value
Last value 5 sec
Last value 10 sec
Substitute value
Substitute value 5 sec
Substitute value 10 sec
Value
Internal value
0.1 ms
0
1 ms
1
8 ms
2
32 ms
3
Off
0
On
1
3ADR010121, 13, en_US
Communication Interface Modules (S500) > PROFINET
Required setting of the
channel parameter "Substi-
tute value"
0
0
0
0
Depending on configuration
Depending on configuration
Depending on configuration
Internal value,
type
BYTE
BYTE
Device Specifications
Default
0.1 ms
0x00
On
0x01
1029