The module provide several diagnosis functions
Further information is provided in the System Technology chapter PROFINET.
1.7.6.4.4
Assignment of the Ethernet Ports
The terminal unit for the communication interface module provides two Ethernet interfaces with
the following pin assignment:
Table 180: Pin assignment RJ45 jack:
Interface
2019/04/17
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply and process voltage) are
switched off before you begin with operations at the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
Pin
1
2
3
4
5
6
7
8
Shield
3ADR010121, 13, en_US
Communication Interface Modules (S500) > PROFINET
Ä Chapter 1.7.6.4.7 "Diagnosis" on page 1077.
Signal
Description
TxD+
Transmit data +
TxD-
Transmit data -
RxD+
Receive data +
NC
not used
NC
not used
RxD-
Receive data -
NC
not used
NC
not used
Cable shield
Functional earth
Device Specifications
1073