ABB AC500 PLC Hardware Manual page 1032

Table of Contents

Advertisement

Device Specifications
Communication Interface Modules (S500) > PROFINET
E1...E4
Class
Byte 4
Bit 6...7
Class
3
3
3
3
4
4
4
4
1032
d1
d2
d3
Comp
Dev
Mod
-
Byte 1
Byte 2
Inter-
Device
Module
face
1
2
3
)
)
)
-
31
31
-
31
31
-
31/1...10 31
-
1...10
31
-
1...10
31
-
1...10
31
-
1...10
31
-
1...10
31
3ADR010121, 13, en_US
d4
Identi-
AC500-
fier
Display
000...06
3
Ch
Err
PS501
PLC
Browser
Byte 3
Byte 4
PNIO
diag-
Bit 0...5
nosis
block
Channel Error-
Error message
Identi-
fier
31
11
Process voltage UP
too low
31
45
No process voltage
UP
31
17
No communication
with I/O device
31
32
Wrong I/O device
type on socket
31
31
At least one
module does not
support failsafe
function
5
8
I/O module
removed from hot-
swap terminal unit
or defective module
on hot-swap ter-
minal unit
5
28
Wrong I/O module
plugged on hot-
swap terminal unit
9
)
5
42
No communication
with I/O module on
hot-swap terminal
unit
<− Display in
Remedy
Check
process
supply
voltage
Check
process
supply
voltage
Replace
I/O
module
Replace
I/O
module /
Check
configu-
ration
Check
modules
and
parame-
terization
Plug I/O
module,
replace
I/O
module
9
)
Remove
wrong
I/O
module
and plug
pro-
jected
I/O
module
Replace
I/O
module
9
)
2019/04/17

Advertisement

Chapters

Table of Contents
loading