The following figure shows the connection of active-type analog sensors (voltage) to differential
analog inputs AI0 and AI1. Proceed with AI2 and AI3 in the same way.
Fig. 153: Connection of active-type analog sensors (voltage) to differential analog inputs
Voltage
Voltage
The measuring ranges are described in the section Measuring Ranges
"Parameterization" on page 794
To avoid error messages from unused analog input channels, configure them as "unused".
Use of Analog Inputs as Digital Inputs
Several (or all) analog inputs can be configured as digital inputs . The inputs are not electrically
isolated against the other analog channels.
The following figure shows the connection of digital sensors to the analog input AI0. Proceed
with the analog inputs AI1 to AI3 in the same way.
790
NOTICE!
Risk of faulty measurements!
The negative pole/earthing potential at the sensors must not have too large a
potential difference with respect to ZP (max. ± 1 V within the full signal range).
Make sure that the potential difference never exceeds ± 1 V.
0...10 V
-10 V...+10 V
Ä Chapter 1.7.2.2.11 "Measuring Ranges" on page 802: